Vaillant F.75 means the pump starts but the pressure sensor doesn't detect the expected pressure change — usually a blocked pressure sensor, air in the system or a faulty pump. First bring the water pressure to 1.2–1.8 bar, bleed the radiators and reset the boiler. If it persists after 2–3 attempts, the pressure sensor or pump needs service.

Offizielle Quelle

vaillant.com.tr

Vaillant Türkiye resmî sitesi

F.75 birkaç adımdan sonra çözülmezse yetkili servis randevusu buradan alınır.

01 — Schritt-für-Schritt-Lösung

Schritt-für-Schritt-Lösung

  1. STEP 01

    Check and refill pressure to 1.2–1.8 bar

    If the display shows below 0.8 bar, F.75 triggers. Open the filling loop under the boiler slowly and close it when the display reaches 1.2–1.8 bar. Make sure the filling tap is fully closed afterwards.

  2. STEP 02

    Bleed the radiators

    Trapped air confuses the pump's pressure detection. Open each radiator's bleed valve slowly; when hissing stops and water appears, close it. Start with the radiators on the highest floor.

    Bleeding drops the pressure by 0.3–0.5 bar; top it back to 1.2–1.8 bar once done.

  3. STEP 03

    Reset the boiler

    Press the reset/power button or switch off the boiler's breaker for 30 seconds. When it restarts, watch whether F.75 returns.

  4. STEP 04

    Open the heating valves fully

    Half-closed flow/return valves cause pressure swings. Make sure the service valves below the boiler are fully open and any filter/dirt trap isn't clogged.

  5. STEP 05

    Check for frozen condensate pipes

    In winter, frozen external pipes stop circulation and can raise F.75. Thaw them first, then reset. Don't force the boiler to run against a frozen system.

    Running the boiler against a frozen system can damage the pump and heat exchanger. Keep the boiler in standby until thawed.

  6. STEP 06

    If it persists: pressure sensor / pump service

    After the steps above, a persistent F.75 points to a blocked or failed pressure sensor or a pump problem. These are authorized-service jobs — don't open the boiler yourself while under warranty.

Tipps

  • An annual system filter cleaning prevents the most common cause: a blocked sensor.
  • Keeping the boiler in summer mode instead of full off prevents pump seizing.
  • Pressure keeps dropping? That's a separate fault — see our 'boiler pressure keeps dropping' guide.

02 — Häufig gestellte Fragen

Häufig gestellte Fragen

Can F.75 clear by itself?

If caused by air or a temporary pressure dip, it clears after refill, bleeding and reset. Sensor blockage or pump failure won't clear without service.

How much does F.75 repair cost?

Typically a pressure sensor cleaning/replacement or pump repair. Under warranty parts and labour are free; otherwise get a quote from authorized service.

Difference between F.75 and F.28?

F.28 is an ignition/flame fault (gas arrives, no flame detected); F.75 is the pressure change not being detected when the pump starts. Both can relate to pressure and air, but the fixes differ.

Hat diese Anleitung geholfen?